Table 4 12 1 1 2 equipment protection but if you have a diesel driven pump you will need sprinklers in the room see below.
Fire pump room sprinkler protection.
A fire sprinkler system is a critical component of life safety in a building.
Fire pumps and their associated equipment can cost from 20 000 to more than 1 000 000 when suction tanks are required and since they are complex pieces of machinery that are vital to the operation of these.
In case of fire in the pump room it happens with diesel engines the sprinkler protection will limit the fire spread and will reduce the time out of service for the pump.
Nfpa 20 4 12 6 ventilation.
4 12 1 3 fire pump buildings or rooms with diesel engines.
Automatic sprinkler system risers fire pumps and controllers shall be provided with ready access.
Some of the pump room or pump house features necessary to protect the pump assembly and satisfy nfpa 20.
In addition many of these spaces have special fire protection systems that are different than run of the mill sprinklers.
Ventilating a diesel fire pump takes a lot more than an electric driven pump.
Standard for the installation of stationary pumps for fire protection protects life and property by providing r equirements for the installation of fire pumps to ensure that systems will work as intended to deliver adequate and reliable water supplies in a fire emergency.
Protection of fire pump room according to nfpa 20.
Fire pump buildings or rooms enclosing diesel engine pump drivers and day tanks shall be protected with an automatic sprinkler system installed in accordance with nfpa 13 as an extra hazard group 2 occupancy.
Fire pump buildings or rooms enclosing diesel engine pump drivers and day tanks must be protected with an automatic sprinkler system.
4 13 1 4 fire pump buildings or rooms with electric drivers.
4 13 1 3 fire pump buildings or rooms with diesel engines.
It is a good practice to protect the diesel fire pump room recommended density is 25 gpm sq ft over the entire room preferably with high temperature sprinklers 286 f.